    Comparing version 10:23, 2 Feb 2018 by fmourao with version 11:06, 2 Feb 2018 by fmourao.

    ...


    ...

    At the present all the software are installed in two IOC serversone IOC server with the exception of the Control System Studio that is also used for the GUI management.

    ...

    Presently there are two instances of EPICS IOC Server implemented. One responsible for the Temperature /Vacuum Node. And a second one, installed in a Raspberry Pi, implemented in the new control unit launched at ISTTOK for the remote control of the vacuum pumps, named Central Node.is installed a prototype unit with the following peripheral nodes:

    Temperature/Vacuum Node: VacuumVacuum System

    ...


    Temperature/Vacuum Node: Temperature Sensors and ELCO Voltage Measurement Systems

    ...

    Central Node

    - Pffeifer rotatory vacuum pump
    - Edwards electro valve
    - Seiko Seiki turbomolecular pump and control unit

    ...

    There are: one control signal to turn the rotatory pump on and off; one control signal to open and close the Edwards electro valve; and four control signals, as well as four monitoring signals for the Seiko Seiki turbomolecular pump and control unit.

    ...

    Process Value in the IOC Server for this system.
    PV Name PV Type Archive
    ISTTOK:central:RotatoryPump bo -
    ISTTOK:central:RotatoryValve bo -
    ISTTOK:central:TMPControllerOn bo -
    ISTTOK:central:TMPControllerOnInv calcout -
    ISTTOK:central:TMPControllerOff bo -
    ISTTOK:central:TMPControllerOffInv calcout -
    ISTTOK:central:TMPMotorOn bo -
    ISTTOK:central:TMPMotorOnInv calcout -
    ISTTOK:central:TMPMotorOff bo -
    ISTTOK:central:TMPMotorOffInv calcout -
    ISTTOK:central:Turbo_PW_Ind bi -
    ISTTOK:central:Turbo_Emergency bi -
    ISTTOK:central:Turbo_Acceleration bi -
    ISTTOK:central:Turbo_NormalOperation bi -
    ISTTOK:central:TMPManualValve bo -

    ...

    Version from 10:23, 2 Feb 2018

    This revision modified by fmourao (Ban)

    ...


    ...

    At the present all the software are installed in one IOC server with the exception of the Control System Studio that is also used for the GUI management.

    ...

    Presently is installed a prototype unit with the following peripheral nodes:

    ...

    Version as of 11:06, 2 Feb 2018

    This revision modified by fmourao (Ban)

    ...


    ...

    At the present all the software are installed in two IOC servers with the exception of the Control System Studio that is also used for the GUI management.

    ...

    Presently there are two instances of EPICS IOC Server implemented. One responsible for the Temperature /Vacuum Node. And a second one, installed in a Raspberry Pi, implemented in the new control unit launched at ISTTOK for the remote control of the vacuum pumps, named Central Node.

    Temperature/Vacuum Node: Vacuum System

    ...


    Temperature/Vacuum Node: Temperature Sensors and ELCO Voltage Measurement Systems

    ...

    Central Node

    - Pffeifer rotatory vacuum pump
    - Edwards electro valve
    - Seiko Seiki turbomolecular pump and control unit

    ...

    There are: one control signal to turn the rotatory pump on and off; one control signal to open and close the Edwards electro valve; and four control signals, as well as four monitoring signals for the Seiko Seiki turbomolecular pump and control unit.

    ...

    Process Value in the IOC Server for this system.
    PV Name PV Type Archive
    ISTTOK:central:RotatoryPump bo -
    ISTTOK:central:RotatoryValve bo -
    ISTTOK:central:TMPControllerOn bo -
    ISTTOK:central:TMPControllerOnInv calcout -
    ISTTOK:central:TMPControllerOff bo -
    ISTTOK:central:TMPControllerOffInv calcout -
    ISTTOK:central:TMPMotorOn bo -
    ISTTOK:central:TMPMotorOnInv calcout -
    ISTTOK:central:TMPMotorOff bo -
    ISTTOK:central:TMPMotorOffInv calcout -
    ISTTOK:central:Turbo_PW_Ind bi -
    ISTTOK:central:Turbo_Emergency bi -
    ISTTOK:central:Turbo_Acceleration bi -
    ISTTOK:central:Turbo_NormalOperation bi -
    ISTTOK:central:TMPManualValve bo -

    ...

    Powered by MindTouch Core